Specifications DISPLAY LED display: Measured value (PV) display/ 7-segment red LED 4 digits Set value (SV) display/ 7-segment green LED 4 digits Display accuracy: ±(0.25% FS + 1 digit) Range in which display accuracy is maintained: 23 C ± 5 c Display resolution: Depends on measuring range (0.001, 0.01, 0.1, 1) Sampling cycle: 250 msec. (0.25 sec.) Action display/color: 11 types, LED lamp display Control output: (OUT 1, 2) /green Event action: (EV 1, 2,3)/orange Auto tuning action (AT) / green Manual control action (MAN) /green Set value bias action (SV2 / SB) /green Remote action (REM) / green Standby action (STBY) / green Comm. status (COM/RUN)/green SETTING
Setting method: By front key switch operation Setting range: Same as measuring range (within setting limiter) Setting limiter: Higher and lower limits separate setting; free within measuring range (Lower limit< higher limit) Set value resolution: Depends on range and scaling (0.001, 0.01, 0.1, 1) Setting key type: 6 types - PARA (parameter selection), UP, DOWN, AT, ENT and DISP keys Ramp control upon reaching set value: Ascending/descending ramp control Ramp setting range: OFF, 1 ~ 9999 Units Ramp unit time: /sec, /min switching by front key operation and communication Ramp rate: X 1, X 0.1 switching by front key operation and communication
INPUT Thermocouple: B, R, S, K, E, J, T, N, PL II, WRe5-26, {L, U (DIN 43710) }K, AuFe-Cr Kelvin unit input Allowable external resistance range: 100 Ohm maximum Input impedance: 500k Ohm minimum Burnout function: Standard feature (up scale) Cold junction temp. compensation accuracy: ± 2 C (within a range from 5 to 45 C) R.T.D.: Pt100/ JPt100 Amperage: About 0.25 mA Allowable range of lead wire resistance: 5 Ohm maximum/wire Voltage (multiple input): -10 ~ 10, 0 ~ 10, 0 ~ 20, 0 ~ 50, 10 ~ 50, 0 ~ 100mV DC, or -1 ~ 1, 0 ~ 1, 0 ~ 2, 0 ~ 5, 1 ~ 5, 0 ~ 10V DC Input impedance: 500k Ohm minimum Current: 0 ~ 20mA, 4 ~ 20mA DC Receiving impedance: 250 Ohm Sampling cycle: 250 msec. (0.25 sec.) PV bias: -1999 ~ 1999 Units PV filter: OFF, 1 ~ 100 sec. Cold junction temp. compensation switching: INT (internal) / EXT (external) switching by front key operation
Isolation: Insulated from various outputs (not insulated from system, DI (external switching input) and CT input)
CONTROL (SR82: 1 output only) Control system: One output operation: Expert PID control with auto tuning function RA(reverse characteristics): Heating action DA(due characteristics): Cooling action Two output operation (option): Expert PID + PID (control outputs 1 and 2 individually in action) control with auto tuning function RA (reverse characteristics): Heating action (output 1 side and cooling (output 2 side) DA (due characteristics): 2-stage heating action (by both of control outputs 1 and 2) PID (Control outputs 1 and 2 individually) Control output 1: Proportional band (P); OFF, 0.1~ 999.9% (OFF=ON/OFF action) Integral time (I):OFF, 1 ~ 6000 sec. (OFF= with manual reset) Derivative time (D): OFF, 0 ~ 3600 sec, Manual reset: -50.0 to +50.0% (valid when I=OFF) ON/OFF hysteresis: 1 ~ 1000 unit (valid during ON/OFF action) Control output 2 (only when two output option is added): Proportional band (P): OFF, 0.1~ 999.9% (OFF=ON/OFF action) Integral time (I): OFF, 1 ~ 6000 sec. Derivative time (D): OFF, 0 ~ 3600 sec. ON/OFF hysteresis: 1 ~ 1000 Units (valid during ON/OFF action) Dead band: -1999 ~ 5000 Units Separate setting for SB/SV2 is possib1e~ Setting range is the same as the one listed above. Proportional cycle: (for contact and SSR drive voltage output) Control output 1: 1 ~ 120sec. Control output 2: 1 ~ 120 sec. AT point setting: 0-5000 Units Control output characteristics: RA (reverse characteristics)/DA (due characteristics) switchable by front key operation or DI (external switching input) through communication. Higher and lower limit output limiter (individually for control outputs l and 2): Lower limit side: 0.0~99.9%, Higher limit side: 0.1~100.0% on condition that lower limit value higher limit value. Separate setting for SB/SV2 is possible. Setting range is the same as the one listed above. Control output at time of error (individually for control outputs 1 and 2): 0.0 ~ 100.0% Control output type/rating(common to control outputs 1 and 2): Contact (Y): 240V AC 2.5A/resistive load SSR drive voltage (P): 12V± l.5V DC, load current 30mA maximum Current (I): 4~20mA DC, load resistance 600 ohm maximum, Voltage (V): 0~l0V DC, load current 2mA maximum
Output resolution Control output 1: About 0.0125% (1/8000) Control output 2: About 0.5% (1/200) Sampling cycle: 250 msec. (0.25 sec.) Manual control / Manual switching: Front key operation or DI (external switching input) through communication Manual control output: 0.0-100.0% (out of output limiter range possible) Setting resolution: 0.1% Manual / Automatic control: Balanceless / bumpless (within proportional band) Isolation: Insulated between control output and system and various inputs (not insulated between control output of current, voltage or SSR and analog output)
EVENT OUTPUT (optional) Number of event outputs: SR82 - 2 SR83 -3 (2 when 2 output option is added) SR84 -3 (2 when communication option, analog output option and/or 2 output option are added) (In case of 2 event outputs, EV2 and EV3 are common output with OR.) Event type: Selectable from 8 types (7 types when heater break alarm option is not added) A-Hi: Higher limit absolute value alarm A-Lo: Lower limit absolute value alarm D-Hi: Higher limit deviation value alarm D-Lo: Lower limit deviation value alarm D-i: Higher/lower limit deviation value alarm (within range) D-o: Higher/lower limit deviation value alarm (out of range) Sco: Scaleover (input trouble alarm) Hb: Heater break alarm (selectable only when heater break alarm option is added) Event setting range: Deviation value alarm Higher limit alarm: -l999~ 9999 Units Lower limit alarm: -1999~ 9999 Units Higher/lower limit alarm: 0~ 9999 Units Absolute value alarm Both higher and lower limits: Within measuring range Event setting system: By front key operation Event action: ON/OFF action Event hysteresis: 1 ~ 1000 Units Standby/no standby action: Selectable from 5 types Alarm action without standby Alarm action with standby (When power is ON) Alarm action with standby (When power is ON, when standby is switched to execution) Alarm action with standby (When power is ON, when standby is switched to execution, including the time when SV is changed) Control action Event action delay: OFF, 1~ 9999 sec. Event output/rating: Contact 240V AC 1.0A (resistive load) Output updating cycle: 250 msec. (0.25 sec.)
ANALOG OUTPUT (optional, not selectable together with communication type(1) and (2)) The number of analog output: 1 Output signal: Selectable from 5 types (3 types for instrument with one output) PV: Measured value SV: Set value DEV: Bias output OUT 1: Control output I OUT 2: Control output 2 (selectable only when 2 output option is added) Output type/rating: 0~ 10 mV DC/FS Output impedance: 10 ohm 0~ 10 V DC/FS Load current: 2mA maximum 4~ 20mA DC/FS Load resistance: 300 ohm maximum Output scaling PV/SV: Within measuring range (inverted scaling possible) OUT1/OUT2: 0.0-100.0% (inverted scaling possible) DEV: -100.0~ 100.0% (inverted scaling possible) on condition that Ao-L is not equal to Ao-H Output accuracy: (Plus/minus) 0.25% FS (to displayed value) Output resolution: 0.01% FS (1/10000) Output updating cycle: 250 msec. (0.25 sec.) Isolation: Insulated from system and various inputs (not insulated from control outputs I, P and V)
HEATER BREAK ALARM (optional, not selectable together with REM input) Current capacity: 30A or 50A CT to be specified when order is placed. Alarm action: Heater amperage detected by external CT (CT attached) Alarm output ON upon detection of heater break while control output is ON. Alarm output ON upon detection of heater loop alarm while control output is OFF. Current setting range: 0.1 ~ 50.0A (Alarm action stops when OFF is set.) Setting resolution: 0.1 A Current display: 0.0~ 55.0A Display accuracy: Approx. 3% FS (for 50Hz/60Hz sine wave) Minimum time for action confirmation: ON (OFF) time 250 msec. Min Alarm output/rating: Contact 240V AC 1.0A (resistive load) Alarm action display: "Event" lamp lights during action. Alarm holding mode: Switchable between holding and not holding on the setting screen. Sampling time: 500 msec. (0.5 sec,) Isolation: Insulated between CT input and various outputs (not insulated from system and other inputs)
REMOTE (optional, not selectable together with heater break alarm) Remote setting: By external analog signal Switching to remote: By key, communication and DI (external switching) input (valid only when Dl option is added) Remote/local switching function by remote signal Remote switching point: OFF, 0.1 ~50.0% Remote switching hysteresis: 0.1 ~10.0% Remote scaling: Within measuring range (inverted scaling possible) Accuracy of setting: ± (0.25% SF + I digit) Setting signal: 0 ~l0V, 1 ~5V DC Input impedance: 500k ohm 4 ~20mA DC Receiving impedance: 250 ohm Remote bias: -1999 ~1999 units Remote filter: OFF, 1 ~100 sec. Sampling cycle: 500 msec. (0.5 sec.) Isolation: Insulated between remote input and various outputs (not insulated from system and various inputs)
COMMUNICATION (optional, not selectable together with analog output for SR82 and SR84) Communication type (1): RS-232C, RS-485 Communication system: RS-232C 3-line half duplex system RS-485 2-line half duplex multiple drop (bus) system Synchronization system: Start-stop synchronization system Communication distance: RS-232C maximum l5m RS-485 maximum 500m (depending on conditions)
Communication speed: 1200, 2400,4800, 9600, 19200 bps Data bit length: 7 bits, even parity, stop bit 1 7 bits, even parity, stop bit 2 7 bits, no parity, stop bit 1 7 bits, no parity, stop bit 2 8 bits, even parity, stop bit 1 8 bits, even parity, stop bit 2 8 bits, no parity, stop bit 1 8 bits, no parity, stop bit 2 Communication address: 1 ~ 99 Communication memory mode: EEP/RAM/r- E Communication BCC: Add/Add two's cmp/XOR/None Communication delay time: OFF, 1 ~ 100 Communication code: ASCII code Communication protocol: Shimaden standard protocol The-number of instruments allowed to be connected: RS-232C: 1 RS-485: 32 maximum (depending on conditions; host included) Isolation: Insulated between communication signal and various inputs/system/various outputs Communication type (2): Conforming with Mitsubishi Electric Company's CC-Link (only for SR83, simultaneous-selection of analog output is not possible) Transmission speed: 156K, 625K, 2.5M, 5M, 10M bps Private Station: 1 Communication method: Polling method Synchronization method: Frame synchronous method Coding system: NRZI system Transmission line: Bus (RS-485) Transmission format: Conforming with HDLC
DI (EXTERNAL SWITCHING) INPUT (optional) *DI stands for "Digital Input." Number of Dl point: 2 DI input type: Selectable from 8 types (7 types if the remote option is not added.) NOP: No operation STB: Execution/standby SB/SV2: Set value bias/set value 2 AT: Auto tuning MAN: Manual STP: Ramp temporary stop DA: Direct action REM: Remote (selectable only when remote option is added) DI input rating: No-voltage contact, open collector input (about 5V/2mA impress) Isolation: Insulated between DI input and various outputs (not insulated from system and various inputs)
SET VALUE 2 (SV2)/Set Value Bias (SB) (optional) (DI option is prerequisite.) Action input: No-voltage contact by SB/SV2 selection through DI (external switching) input (in action during closed input) Selection of setting: Absolute value setting (SV2) Deviation value setting (SB) Setting range: Absolute value setting: Within measuring range Deviation value setting: -1999 ~ 5000 Units SV2 allows PID and output limit to be set.
OTHERS Data storage: By non-volatile memory (EEPROM) Ambient temperate/humidity ranges for use: -l0 ~ +50 C/below 90% RH (on condition that there is no dew condensation) Temperature for storage: Between -20 and +65 C Temperature range for maintaining accuracy: 23 ± 5 C Power voltage: 100V-240V AC± 10% (50/60 Hz), 24V AC± 10% (50/ 60Hz), 24VDC±l0%. (One of the above to be specified) Power consumption: 12VA maximum Input noise removal ratio: Normal mode 60 dB minimum (50/60Hz) Common mode 140 dB minimum (50/60 Hz) Applicable standards: Safety: lEClOlO-l and EN6IOIO-I EMC: EN50081-2: 1993 (EMI/Emission) EN50082-2: 1995 (EMS/Immunity) Insulation resistance: Between input/output terminals and power terminal 500V DC 20M ohm minimum Between input/output terminals and protective conductor terminal 500V DC 20M ohm minimum Dielectric strength: 1 minute at 2300V AC between input/output terminals and power terminal 1 minute at 1500V AC between power terminal and protective conductor terminal Protective structure: Only front panel has simple dust-proof and drip-proof structure (equivalent to IP66) Material of case: PPO resin molding (equivalent to UL94V-1) External dimensions: SR82: H72 x W72 x D111mm (Inside depth of panel: 100mm) SR83: H96 x W96 x D111mm (Inside depth of panel: 100mm) SR84: H96 x W48 x D111mm (Inside depth of panel: 100mm) Mounting: Push-in panel (one-touch mount) Applicable panel thickness: l.0 ~ 4.0 mm Panel cutout size: SR82: H68 x W68mm; SR83: H92 x W92mm; SR84: H92 x W45mm Weight: SR82: 300g; SR83: 420g; SR84: 280g
User Selectable Inputs & Ranges:
Thermocouples and RTDs
Programmable Ranges:
Voltage, DC Current and DC Millivolts
Front Panel:
Drip Proff and Dust Proof (IP66)
Optional Features:
Dual Output (SR83 & SR84 Only) Heat / Cool
24VDC or 24 VAC
Dual Event Outputs
Event Outputs + 30 Amp Heater Break Alarm
Event Output + 50 Amp Heater Break Alarm
Remote Input
Analog Output
Computer Interface: RS232C or RS485
External Input Control, Set Point Bias
CE Approved & UL/CSA Pending